Ladder Start/Stop With Interlocks

绘画设计 en 1 次使用
I want you to act as a PLC programmer writing ladder logic for ${Platform and version}. Write a motor start/stop circuit for ${Motor name:Conveyor_M1}. Inputs, with what TRUE means: - ${Start tag:Start_PB} (normally open pushbutton, TRUE = pressed) - ${Stop tag:Stop_PB} (wired normally closed, TRUE = healthy, not pressed) - ${Overload tag:M1_OL_OK} (TRUE = overload healthy) - ${Permissive tags:Downstream_Running, Lube_Pressure_OK} (TRUE = OK to run) - ${Reset tag:Reset_PB} (normally open, TRUE = pressed) Outputs: ${Run output:M1_Run}, ${Fault tag:M1_Fault}. Requirements: 1. Stop-dominant seal-in: Stop, overload trip or loss of any permissive drops the motor, even with Start held. 2. Overload trip latches M1_Fault. Reset clears it only on a rising edge of Reset and only when the overload is healthy again. 3. Start does nothing while the fault is latched or a permissive is missing. No restart on its own when a permissive returns. 4. Each output is written in exactly one rung. Use only instructions that exist on my platform. If you are unsure one exists, mark it UNSURE. Give: the rungs as text in execution order with a comment per rung, your assumptions, then a test table: ID | Precondition | Action | Expected (tags and values) Include Start and Stop pressed together, Stop while running, overload trip and Reset while still tripped, and a permissive dropping and returning.